One digital input and one SPDT relay per equal-status node, with automatic signal forwarding
Y403-11-L LoRa Auto Relay Wireless I/O, 1DI/1DO
1DI+1DO LoRa Multi-Node Wireless I/O Module
Y403-11-L uses equal-status LoRa nodes to forward switching signals automatically. Any closed input energizes all node relays for coordinated non-safety control.

Key Features
Any closed input energizes every node output, including the local relay; all inputs must open before the outputs reset
Up to 5 km per hop standard in open areas; selected 10 km configurations depend on antennas and installation
Passive dry-contact/NPN inputs, 5 A relay contacts at 277 VAC or 28 VDC, and 9–36 VDC power
For auxiliary signaling and non-safety control; relay hops add latency and the system is not certified for emergency-stop use
Specifications
Wireless
- Frequency Band
- 398~525 MHz
- Communication Range
- Up to 5 km per hop standard; 10 km option for selected configurations (open area; antenna and site dependent)
- Relay Extension
- Extended through node-to-node relaying
- Antenna Connector
- SMA
- Standard Antenna
- 470 MHz magnetic-mount antenna
Power Supply
- Voltage
- DC 9~36V
- Max Power Consumption
- 1W
- Operating Temperature
- -20°C ~ +85°C
- Humidity
- 10% ~ 90% RH, non-condensing
Digital Inputs
- Channels
- 1
- Type
- Passive dry contact / NPN open-collector (no voltage input to DI)
Digital Outputs
- Channels
- 1
- Type
- SPDT relay
- Rating
- AC 277V 5A / DC 28V 5A
Mechanical
- Dimensions
- 88 x 37 x 59 mm
- Weight
- Approx. 50 g
- Mounting
- 35 mm DIN rail
- Protection
- IP20
Product Documents
Related Products
Talk to our technical team.
Tell us about your interfaces, network environment, and deployment requirements.