Y301-200 2-Channel RS485 Modbus Pulse Counter Module

2DI I/O Module

Y301-200 reads two opto-isolated digital inputs over RS485 Modbus RTU, with 32-bit pulse counting, configurable debounce, and count retention after power loss.

  • Modbus-RTU
  • RS485
  • Digital Input
  • Pulse Counter
  • DIN Rail

Key Features

01

Two dry/wet contact inputs for status monitoring and pulse counting

02

32-bit accumulated counts are retained after power loss

03

Selectable rising or falling counting edge with 5-255 ms debounce

04

RS485 Modbus RTU, optional RS232 or TTL, and software-configurable address 1-255

05

Input-only design with a 5-36 VDC supply and 80 mA typical current at 12 V

Specifications

Power Supply

Voltage
DC 5~36V
Typical Current
80 mA @ 12 V
Operating Temperature
-40°C ~ +85°C
Humidity
5% ~ 95% RH, non-condensing

Digital Inputs

Channels
2
Type
Dry/wet contact, opto-isolated
Voltage Range
5-36 VDC (wet contact; confirm permitted voltage for supplied hardware before connection)
Sampling Rate
100 Hz
Pulse Counter
32-bit, selectable rising/falling edge
Debounce
5~255 ms (default 50 ms)
Counter Retention
Accumulated counts are retained after power loss

Communication

Interfaces
RS485 (2-wire), optional RS232 or TTL
Protocol
Modbus RTU slave
Baud Rate
600~230400 bps (default 9600)
Slave Address
1-255 (software configurable; default 1)

Mechanical

Dimensions
77.4 x 22.5 x 16.2 mm
Mounting
DIN rail or screw mounting

Talk to our technical team.

Tell us about your interfaces, network environment, and deployment requirements.

Get Selection Advice