Y301-800 8-Channel Modbus Digital Input Module

8-Channel Isolated Digital Input Module

Y301-800 monitors eight opto-isolated switch inputs in control cabinets, with dry-contact or 3.3-24 VDC wiring and RS485/RS232 Modbus RTU/ASCII.

  • Modbus-RTU
  • RS485
  • Digital Input
  • DIN Rail

Key Features

01

Eight opto-isolated digital inputs for cabinet switch monitoring

02

Accepts dry contacts and active voltage signals from 3.3 to 24 VDC

03

Modbus RTU or ASCII over RS485 or RS232, with input states read by function code 0x02

04

Selectable baud rates of 2400, 4800, 9600, 19200, or 38400 bps

05

35 mm DIN-rail installation, 7-30 VDC power, and -40 to +85 C operation

Specifications

Power Supply

Voltage
DC 7~30V
Operating Temperature
-40°C ~ +85°C

Digital Inputs

Channels
8
Input Type
Opto-isolated discrete input
Wiring Mode
Dry contact / active input
Active Input Voltage
3.3~24V DC
Read Method
Function code 0x02 (discrete inputs)

Communication

Interfaces
RS485 or RS232 (configuration option)
Protocol
Modbus RTU / Modbus ASCII
Default Serial Format
9600, N, 8, 1
Optional Baud Rates
2400 / 4800 / 9600 / 19200 / 38400 bps
Address Range
0-255; address 0 is not for normal communication; broadcast 254 is for single-device setup only

Mechanical

Dimensions
120 x 70 x 35 mm
Weight
Approx. 60 g
Mounting
35 mm DIN rail

Talk to our technical team.

Tell us about your interfaces, network environment, and deployment requirements.

Get Selection Advice