Y301-110 RS485 Modbus I/O Module with 1 DI and 1 Relay

1DI+1DO I/O Module

Y301-110 pairs one opto-isolated input with one SPDT relay for local alarms and actuator control, using RS485 Modbus RTU and two onboard automation rules.

  • Modbus-RTU
  • RS485
  • Digital Input
  • Relay Output
  • Mini Module
  • DIN Rail

Key Features

01

One dry/wet contact input and one SPDT relay rated 125 VAC 0.5 A or 30 VDC 2 A

02

32-bit pulse counting with selectable edge and 5-255 ms debounce

03

Two local rules for DI-to-relay control, pulse output, or timed switching

04

RS485 Modbus RTU with optional RS232 or TTL and software-only addressing

05

5-36 VDC supply in a 77.4 x 22.5 x 16.2 mm module; DO state retention is not supported

Specifications

Power Supply

Voltage
DC 5~36V
Typical Current
80 mA @ 12 V
Operating Temperature
-40°C ~ +85°C
Humidity
5% ~ 95% RH, non-condensing

Digital Inputs

Channels
1
Type
Dry/wet contact, opto-isolated
Voltage Range
5-36 VDC (wet contact; confirm permitted voltage for supplied hardware before connection)
Sampling Rate
100 Hz
Pulse Counter
32-bit, selectable rising/falling edge
Debounce
5~255 ms (default 50 ms)

Digital Outputs

Channels
1
Type
SPDT relay
Contact Rating
125 VAC 0.5 A / 30 VDC 2 A
Electrical Life
100,000 cycles
Output Retention
Not supported

Communication

Interfaces
RS485 (2-wire), optional RS232 or TTL
Protocol
Modbus RTU slave
Baud Rate
600~230400 bps (default 9600)
Slave Address
1-255 (software configurable; default 1)

Mechanical

Dimensions
77.4 x 22.5 x 16.2 mm
Mounting
DIN rail or screw mounting

Talk to our technical team.

Tell us about your interfaces, network environment, and deployment requirements.

Get Selection Advice